1MRS 755537
Motor protection Relay
Technical Reference Manual
Table 4.1.4.12-1 Setting values
Setting
Description
66
Restart disable value
66 COOL/∆t
Countdown rate of start-up time
counter
Trip Fail
Operate time of CBFAIL
RTD1A
Alarm value RTD1A
RTD1A TDLY
Operate time RTD1A TDLY
RTD1T
Trip value RTD1T
RTD1T TDLY
Operate time RTD1T TDLY
RTD2A
Alarm value RTD2A
RTD2A TDLY
Operate time RTD2A TDLY
RTD2T
Trip value RTD2T
RTD2T TDLY
Operate time RTD2T TDLY
RTD3A
Alarm value RTD3A
RTD3A TDLY
Operate time RTD3A TDLY
RTD3T
Trip value RTD3T
RTD3T TDLY
Operate time RTD3T TDLY
RTD4A
Alarm value RTD4A
RTD4A TDLY
Operate time RTD4A TDLY
RTD4T
Trip value RTD4T
RTD4T TDLY
Operate time RTD4T TDLY
RTD5A
Alarm value RTD5A
RTD5A TDLY
Operate time RTD5A TDLY
RTD5T
Trip value RTD5T
RTD5T TDLY
Operate time RTD5T TDLY
RTD6A
Alarm value RTD6A
RTD6A TDLY
Operate time RTD6A TDLY
RTD6T
Trip value RTD6T
RTD6T TDLY
Operate time RTD6T TDLY
PTC1
Trip value PTC1
PTC2
Trip value PTC2
1)
The FLA secondary scaling factor has only one setting and thus switching between setting groups
does not apply.
2)
The setting step is 0.5.
REM 610
Default
Setting range
setting
5...500 s
5 s
2...250 s/h
2 s/h
0.10...60.0 s
0.10 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0.1...15.0 kΩ
0.1 kΩ
0.1...15.0 kΩ
0.1 kΩ
41