ABB REM 610 Technical Reference Manual page 44

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
44
Motor Protection Relay
Technical Reference Manual
Table 4.1.4.12-3 SGF2
Switch
Function
SGF2/1
Operation mode of the alarm target of element 49
SGF2/2
Operation mode of the pickup target of element 48/14
SGF2/3
Operation mode of the pickup target of element 50P
SGF2/4
Operation mode of the pickup target of element 37
SGF2/5
Operation mode of the pickup target of element 51N
SGF2/6
Operation mode of the pickup target of element 46
SGF2/7
Operation mode of the alarm target of element 49/38-1
SGF2/8
Operation mode of the alarm target of element 49/38-2
• 0 = the pickup target will automatically be cleared once the
fault has disappeared
• 1 = latching. The pickup target will remain active although the
fault has disappeared.
ΣSGF2
1)
In addition, the phase(s) which caused the pickup will be shown on the LCD.
Table 4.1.4.12-4 SGF3
Switch
Function
SGF3/1
Disable of element 50P
SGF3/2
Disable of element 37
SGF3/3
Disable of element 51N
SGF3/4
Disable of element 46
SGF3/5
Disable of element 46R
• When the switch is in position 1, the element is disabled.
SGF3/6
Start-up supervision
• 0 = based on thermal stress calculation
• 1 = based on definite-time overcurrent protection
SGF3/7
Pickup criteria for element (48/14 PICKUP)
• 0 = the element will pickup when the conditions for motor start
up are met
• 1 = the element will pickup when one or several phase
currents exceed the set pickup value
SGF3/8
Automatic doubling of the pickup value of element 50P
• When the switch is in position 1, the set pickup value of the
element will automatically be doubled at high inrush situations
ΣSGF3
1MRS 755537
Default
setting
0
1)
0
1)
0
1)
0
0
0
0
0
0
Default
setting
0
1
0
0
0
0
0
2
x (48/14 TDLY)
0
2