ABB REM 610 Technical Reference Manual page 106

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
106
Motor Protection Relay
Technical Reference Manual
Fig. 4.2.2.-1
Jumper location on the RS-485 communication module
Table 4.2.2-2
RS-485 rear connector
Terminal
Function
X5.5-6
Data A (+)
X5.5-5
Data B (-)
X5.5-4
Signal GND (for potential balancing)
X5.5-3
-
X5.5-2
Shield GND (via capacitor)
X5.5-1
Shield GND
Combined fibre-optic connection (plastic and glass)
If REM 610 is provided with the optional fibre-optic communication module for
plastic and glass fibre, the plastic fibre-optic cables are connected to terminals X5.3-
RX (Receiver) and X5.3-TX (Transmitter) and the glass fibre-optic cables to
terminals X5.4-RX (Receiver) and X5.4-TX (Transmitter).
The fibre-optic interface is selected with jumpers X6 and X2 located on the PCB of
the communication module (see Fig. 4.2.2.-2).
Table 4.2.2-3
Transmitter selection
Transmitter
Plastic
Glass
Position of jumper X6
X5.3-TX
X5.4-TX
1MRS 755537

Advertisement

Table of Contents
loading

Table of Contents