ABB REM 610 Technical Reference Manual page 43

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS 755537
Motor protection Relay
Technical Reference Manual
SGF1...SGF5
Switchgroups SGF1...SGF5 are used for configuring the desired function as follows:
Table 4.1.4.12-2 SGF1
Switch
Function
SGF1/1
Selection of the latching feature for PO1
SGF1/2
Selection of the latching feature for PO2
SGF1/3
Selection of the latching feature for PO3
• When the switch is in position 0 and the measuring signal
which caused the trip falls below the set pickup value, the
output contact will return to its initial state.
• When the switch is in position 1, the output contact will remain
active although the measuring signal which caused the trip
falls below the set pickup value.
A latched output contact can be unlatched either via the HMI, a
digital input or the serial bus.
SGF1/4
Minimum pulse length for SO1 and SO2
• 0=80 ms
• 1=40 ms
SGF1/5
Minimum pulse length for PO1, PO2 and PO3
• 0=80 ms
• 1=40 ms
Note!
The latching feature being selected for PO1, PO2 and PO3 will
override this function.
SGF1/6
CBFAIL
• 0 = CBFAIL is not in use
• 1 = the signal to PO1 will start a timer which will generate a
delayed signal to PO2, provided that the fault is not cleared
before the CBFAIL operate time has elapsed.
SGF1/7
Restart disable function
• When the switch is in position 0, the restart disable signal will
be routed to PO3.
• When the switch is in position 1, the restart disable signal will
not be routed to PO3.
SGF1/8
External fault warning
• When the switch is in position 1, the warning signal from the
trip-circuit supervision is routed to SO2.
Note!
To avoid conflicts, SGR5 should be set to 0 when SGF1/8=1.
ΣSGF1
REM 610
Default
setting
0
0
0
0
0
0
0
0
0
43