ABB REM 610 Technical Reference Manual page 112

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
112
Motor Protection Relay
Technical Reference Manual
Table 4.2.3-13 Standard tests
Insulation tests
Dielectric tests
• Test voltage
Impulse voltage test
• Test voltage
Insulation resistance measurements
• Isolation resistance
Mechanical tests
Vibration tests (sinusoidal)
Shock and bump test
Table 4.2.3-14 Data communication
Rear interface, connector X5.3, X5.4 or X5.5
• Fibre-optic or RS-485 connection
• SPA bus, IEC 60870-5-103 or Modbus protocol
• 9.6 or 4.8 kbps (additionally 2.4, 1.2 or 0.3 kbps for Modbus)
Front interface
• Optical connection (infrared): wirelessly or via the front communication cable
(1MRS050698)
• SPA bus protocol
• 9.6 or 4.8 kbps (9.6 kbps with front communication cable)
Auxiliary voltage
The REM 610 requires a secured auxiliary voltage supply to operate. The internal
power supply of the relay forms the voltages required by the relay electronics. The
power supply is a galvanically isolated (flyback-type) DC/DC converter. When the
auxiliary voltage is connected, the green target LED (ready) on the front panel will
be on. For detailed information on power supply, refer to table 4.2.3-2.
The primary side of the power supply is protected with a fuse located on the PCB of
the relay.
1MRS 755537
According to the IEC 60255-5
2 kV, 50 Hz, 1 min
According to the IEC 60255-5
5 kV, unipolar impulses, waveform
1.2/50 µs, source energy 0.5 J
According to the IEC 60255-5
>100 MΩ, 500 V dc
According to the IEC 60255-21-1,
class I
According to the IEC 60255-21-2,
class I