REM 610
94
Motor Protection Relay
Technical Reference Manual
Channel 0
Events always included in the event reporting:
Table 4.1.15.1-2 Event codes E1...E7
Channel Event Description
0
E1
IRF
0
E2
IRF disappeared
0
E3
Warning
0
E4
Warning disappeared
0
E5
Emergency start activated
0
E6
Emergency start deactivated
0
E7
The thermal level has been changed via serial
communication
Table 4.1.15.1-3 Event codes E50...E51
Channel Event Description
0
E50
Restart of relay
0
E51
Overflow of event buffer
Events possible to mask out:
Table 4.1.15.1-4 Event codes E31...E34
Channel Event Description
0
E31
Disturbance recorder triggered
0
E32
Disturbance recorder memory cleared
0
E33
HMI password opened
0
E34
HMI password closed
Default value of event mask V155
Channel 1
Table 4.1.15.1-5 Event codes E1...E14
Channel Event Description
1
E1
Motor start up begins
1
E2
Motor start up ends
1
Pickup of element 49 activated
1)
E3
1
1)
Pickup of element 49 reset
E4
1
E5
Alarm signal from element 49 activated
1
E6
Alarm signal from element 49 reset
1
E7
Trip signal from element 49 activated
1
E8
Trip signal from element 49 reset
1
E9
Restart disable signal from element 49
activated
1
E10
Restart disable signal from element 49 reset
1
E11
Restart disable signal from element 66
activated
1
E12
Restart disable signal from element 66 reset
1
E13
Restart disable activated
Weighting
factor
1
2
4
8
Weighting
factor
1
2
4
8
16
32
64
128
256
512
1024
2048
2)
4096
1MRS 755537
Default value
1
0
0
0
1
Default value
0
0
1
0
1
0
1
0
0
0
0
0
1