ABB REM 610 Technical Reference Manual page 37

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS 755537
Motor protection Relay
Technical Reference Manual
Fig. 4.1.4.11.-1 RTD sensor/thermistor connection
RTD temperature vs resistance
Resistance values (Ω) of RTD sensors at specified temperatures are presented in the
table below.
Table 4.1.4.11-1 Resistance values of RTD sensors
Platinum
TCR 0.00385
Temperature °C
Pt 100
-40
84.27
-30
88.22
-20
92.16
-10
96.09
0
100.00
10
103.90
20
107.79
30
111.67
40
115.54
50
119.40
60
123.24
70
127.07
80
130.89
90
134.70
100
138.50
120
146.06
140
153.58
150
-
160
161.04
180
168.46
200
175.84
220
-
240
-
Nickel
TCR 0.00618
Pt 250
Pt 1000 Ni 100 Ni 120 Cu 10
210.68
842.7
79.1
220.55
882.2
84.1
230.4
921.6
89.3
240.23
960.9
94.6
250
1000
100.0
259.75
1039
105.6
269.48
1077.9
111.2
279.18
1116.7
117.1
288.85
1155.4
123.0
298.5
1194
129.1
308.1
1232.4
135.5
317.68
1270.7
141.7
327.23
1308.9
148.3
336.75
1347
154.9
346.25
1385
161.8
365.15
1460.6
176.0
383.95
1535.8
190.9
-
-
198.6
402.6
1610.4
206.6
421.15
1684.6
223.2
439.6
1758.4
240.7
-
-
259.2
-
-
278.9
REM 610
+
-
+
-
Copper
Nickel
TCR 0.00427
TCR 0.00672
Ni 120 US
94.92
7.49
92.76
100.92 -
-
107.16 8.26
106.15
113.52 -
-
120
9.04
120.00
126.72 -
-
133.44 9.81
134.52
140.52 -
-
147.6
10.58
149.79
154.92 -
-
162.36 11.352
165.90
170.04 -
-
177.96 12.12
182.84
185.88 -
-
194.16 12.90
200.64
211.2
13.67
219.29
229.08 14.44
238.85
238.32 -
-
247.92 15.22
259.30
267.84 -
280.77
288.84 -
303.46
311.04 -
327.53
334.68 -
353.14
37