ABB REM 610 Technical Reference Manual page 140

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
140
Motor Protection Relay
Technical Reference Manual
Table 10.-2Setting group 2
Variable
Checksum, SGL 6
Checksum, SGL 7
Checksum, SGL 8
Table 10.-3Control parameters
Description
FLA secondary (protected
unit scaling factor)
Rated frequency
Time setting range for
demand values in minutes
Non-volatile memory
settings
Time setting for disabling
new trip targets on the
LCD
Trip-circuit supervision
Sensor/thermistor
selection for input RTD1
Sensor selection for input
RTD2
Sensor selection for input
RTD3
Group/
Channel 2
Setting range
(R, W, P)
2S96
0...1048575
2S97
0...1048575
2S98
0...1048575
Parameter
Setting range
(channel 0)
V103
0.50...2.50
V104
50 or 60 Hz
V105
0...999 min
V106
0...63
V108
0...999 min
V113
0 = not in use
1 = in use
V121
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
V122
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
V123
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
1MRS 755537
Default
Customer's
setting
setting
0
0
0
Default
Customer's
setting
setting
1.00
50 Hz
10 min
63
60 min
0
0
0