Table 4.1.4.12-5 SGF4
Switch
Function
SGF4/1 and
Disable of element 51N when one or several phase currents
SGF4/2
exceed the FLA of the motor
x 4
x 6
x 8
SGF4/3
Selection of ambient temperature
• 0 = set ambient temperature
• 1 = ambient temperature from RTD6
If the RTD module has not been installed, the set ambient
temperature will be used.
ΣSGF4
Table 4.1.4.12-6 SGF5
Switch
Function
SGF5/1
Selection of the latching feature for programmable LED1
SGF5/2
Selection of the latching feature for programmable LED2
SGF5/3
Selection of the latching feature for programmable LED3
SGF5/4
Selection of the latching feature for programmable LED4
SGF5/5
Selection of the latching feature for programmable LED5
SGF5/6
Selection of the latching feature for programmable LED6
SGF5/7
Selection of the latching feature for programmable LED7
SGF5/8
Selection of the latching feature for programmable LED8
• When the switch is in position 0 and the signal routed to the
LED is reset, the programmable LED will be cleared.
• When the switch is in position 1, the programmable LED will
remain lit although the signal routed to the LED is reset.
A latched programmable LED can be cleared either via the
HMI, a digital input or the serial bus.
ΣSGF5
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of switchgroup
SGB1, the DI2 signal with those of SGB2, and so forth.
Table 4.1.4.12-7 SGB1...SGB5
Switch
Function
SGB1...5/1
• 0 = targets are not cleared by the digital input signal
• 1 = targets are cleared by the digital input signal
SGB1...5/2
• 0 = targets are not cleared and latched output contacts are not
unlatched by the digital input signal
• 1 = targets are cleared and latched output contacts are
unlatched by the digital input signal
SGF4/1
SGF4/2
0
1
1
0
1
1
REM 610
Default
setting
0 0
0
0
Default
setting
0
0
0
0
0
0
0
0
0
Default
setting
0
0
45