ABB REM 610 Technical Reference Manual page 141

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS 755537
Motor protection Relay
Technical Reference Manual
Table 10.-3Control parameters
Description
Sensor/thermistor
selection for input RTD4
Sensor selection for input
RTD5
Sensor selection for input
RTD6
Remote control of settings V150
Unit address of the relay
Data transfer rate (SPA),
kbps
Rear communication
protocol
Connection type
Line-idle state
Optional communication
module
Table 10.-4 Parameters for the disturbance recorder
Parameter
Description
(Channel 0)
Sampling rate
M15
Station identification/
M18
unit number
Name of the motor
M20
drive
Parameter
Setting range
(channel 0)
V124
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
V125
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
V126
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
0 = setting group 1
1 = setting group 2
V200
1...254
V201
9.6/4.8
V203
0 = SPA
1 = IEC_103
2 = Modbus RTU
3 = Modbus ASCII
V204
0 = loop
1 = star
V205
0 = light off
1 = light on
V206
0 = not in use
1 = in use
Setting range
800/960 Hz
400/480 Hz
50/60 Hz
0...9999
Max 16 characters
REM 610
Default
Customer's
setting
setting
0
0
0
0
1
9.6
0
0
0
0
Default
Customer's
setting
settings
800 Hz
0
- ABB -
141

Advertisement

Table of Contents
loading

Table of Contents