Stop Signal
A stop signal includes the following:
Removal of start signal via contacts 3 and 4. An ATS
D
(used during a power outage, exercise period, etc.) or
a remote panel used in the vessel take precedence
over all other start signals.
System Stop (AUTO-OFF). Press AUTO and OFF
D
simultaneously to send a stop signal to cancel the
system start.
Note: This will not do anything if the system start is
not active or if the system is receiving a start
signal from another source. Press AUTO
and OFF on any controller in the system.
Communications-based
D
SiteTecht or a CAN-based remote panel.
Engine Cooldown
Cooldown is a state where the generator is running at no
load to allow hot engine components time to cool slowly
before the engine is stopped. In paralleling applications,
this occurs with the circuit breaker open.
When the generator set is running in AUTO mode
(AUTO-RUN), an engine cooldown cycle begins when
the remote start input is deactivated. Also, if stopping
due to a stop signal, a cooldown cycle begins.
Button Mode
AUTO
OFF/RESET
RUN
(unit fails to start)
RUN
(unit starts)
* The alarm horn on/off is based on SiteTecht parameter settings.
Figure 2-3 Button Function Summary
TP-7126 5/20
stop
message
from
Generator Set
Status
Fault Lamp
Off
On (or Cranking)
Running and then
Red
Off
Off
Yellow
Off (or Cranking)
Yellow
Off
Red
Off (or Cranking)
Yellow
On
Running and then
Red
Off
If the Cooldown Override is disabled (OFF) in the
Generator Configuration Menu, coolant temperature is
ignored. The generator will enter cooldown when the
start signal is removed, only if in AUTO. The engine will
run for a period of time equal to the Cooldown Delay
parameter setting, regardless of the coolant temperature.
If the Cooldown Override is enabled (ON) in the
Generator Configuration Menu, coolant temperature will
be considered for cooldown. The generator will enter
cooldown when the start signal is removed, only if in
AUTO. The engine will run until the coolant temperature
is below the Engine Cooled Down parameter setting, or
until the Cooldown Delay has expired.
The cooldown cycle lasts for some predetermined
amount of time. The cooldown delay is an adjustable
parameter. The Engine Cooled Down temperature is
not adjustable.
Note: No engine cooldown cycle occurs if the OFF
button is pressed or if a fault occurs.
shutdown is immediate.
generator set without load for 5 minutes to ensure
adequate engine cooldown.
Alarm
Alarm Silence
Alarm
Horn *
Button
Horn Lamp
Off
Off
On
Off
Pressed
Yellow
On
Off
Pressed
Yellow
On
Off
Pressed
Yellow
On
Off
Pressed
Yellow
On
Off
Pressed
Yellow
On
Off
Pressed
Yellow
If possible, run the
Controller Display
Scrolling Overview Menu
Only
Shutdown Message
Not In Auto Warning
(Depending on SiteTecht
parameter setting)
Not in Auto Warning
(Depending on SiteTecht
parameter setting)
Locked Rotor Shutdown (or
other shutdown message)
Not in Auto Warming
(Depending on SiteTecht
parameter setting)
Shutdown Message
Section 2 Operation
The
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

350eozcs450efozcs300efozcs

Table of Contents