Engine Start Delay displays the time delay before
D
the generator set starts while the master switch is in
AUTO or RUN positions.
Starting Aid Delay displays the engine starting aid
D
activation time.
Crank On Delay displays the time allocated for
D
generator set crank on in seconds.
Crank Pause Delay displays the time allocated for
D
generator set crank pause in seconds.
Engine Warmed Up displays the temperature
D
when the engine is warmed up enough to be
loaded.
Engine Cooled Down displays the temperature
D
below which the engine cooldown can be
overridden.
Cooldown Delay displays the time delay for
D
engine cooldown while the master switch is in the
AUTO or RUN positions and not in the idle mode.
Cooldown Override allows the user to select the
D
Cooldown Temperature Override Mode. If set to
ON, the engine will stop immediately if the coolant
temperature is below the engine cooled threshold,
but will run for the duration of the cooldown cycle
otherwise. If set to OFF, the engine will always
complete the cooldown cycle.
Fuel Type displays the programmer entered fuel
D
type as NG (Natural Gas), LP (Liquefied
Petroleum), Gasoline, Diesel, or Unknown.
Crank Cycles Limit displays the programmer
D
entered crank cycle.
Enable NFPA Defaults: Allows the user to Enable
D
or Disable the NFPA defaults.
Enable Emergency Battlemode: Allows the user
D
to turn On/Off the emergency battlemode feature.
Note: Conditional for certain units.
24
Section 1 Specifications
Protection Configuration
Note: The time delays are user adjustable using
SiteTecht. Have setup and adjustments of
the
Decision-Makerr
performed only by an authorized Kohler
distributor/dealer.
adjustments are password protected.
Overvoltage displays the percentage of the
D
system voltage that the generator voltage must
exceed for an overvoltage condition to be
indicated. The overvoltage value in volts is also
displayed.
Overvoltage Delay displays the time that the
D
generator voltage must be in an overvoltage
condition before a fault is indicated.
Undervoltage displays the percentage of the
D
system voltage that the generator voltage must
drop below for an undervoltage condition to be
indicated. The undervoltage value in volts is also
displayed.
Undervoltage Delay displays the time that the
D
generator voltage must be in an undervoltage
condition before a fault is indicated.
Overfrequency displays the percentage of the
D
system frequency that the generator frequency
must exceed for an overfrequency condition to be
indicated. The overfrequency value in Hz is also
displayed.
Underfrequency displays the percentage of the
D
system frequency that the generator frequency
must drop below for an under frequency condition
to be indicated. The underfrequency value in Hz is
also displayed.
Overspeed displays the percentage of the engine
D
speed that the engine must exceed for an
overspeed condition to be indicated.
overspeed value in Hz and RPM is also displayed.
Low Battery Voltage displays the system battery
D
voltage that the battery voltage must drop below for
a low battery voltage condition to be indicated. The
low battery voltage in VDC is also displayed.
High Battery Voltage displays the system battery
D
voltage that the battery voltage must exceed for a
high battery voltage condition to be indicated. The
high battery voltage in VDC is also displayed.