Event History Submenu; Configuration Submenu - Kohler 500EOZCS Operation

Commercial marine generator sets
Table of Contents

Advertisement

Last Start displays the date when the generator
D
set last operated.
Last Run Length displays the length of time that
D
the engine ran the last time it was started via the
generator set controller.
Controller Serial No. displays the controller serial
D
number.
Software Version displays the software version
D
number. Use the version number to determine if an
upgrade is needed and/or when troubleshooting
the controller.
ECM Serial No. displays the ECM serial number.
D
Genset Model No. displays the generator set
D
model number. Only adjustable from SiteTecht.
Genset Spec No. displays the generator set
D
specification number.
SiteTecht.
Genset Serial No. displays the generator set serial
D
number. Only adjustable from SiteTecht.
Alternator Part No. displays the alternator part
D
number. Only adjustable from SiteTecht.
Engine Part No. displays the engine part number.
D
Only adjustable from SiteTecht.
Engine Model No. displays the engine model
D
number. Only adjustable from SiteTecht.
Engine Serial No. displays the engine serial
D
number. Only adjustable from SiteTecht.
1.7.2

Event History Submenu

Generator Event History:
This menu allows the user to review up to 1000 entries of
generator system events including shutdown faults,
warning faults, notices, and status events with date and
time stamp. See 1.9.1 Controller Fault Diagnostics for a
list of the items that appear on the Generator Event
History.
Engine Event Log:
A message is sent each time there is a change in a
monitored engine condition (i.e. fault becomes active,
fault is cleared). Upon broadcast of this message, the
controller will request another message that contains
the following information for each fault:
SPN (Suspect Parameter Number) is a four-digit
D
code that represents an engine component.
TP-7126 5/20
Only adjustable from
FMI (Failure Mode Indicator) is a two-digit code
D
that represents the type of fault that occurred (i.e.
short circuit, out of range).
Occurrence Count is a count of how many times a
D
fault has occurred.
1.7.3

Configuration Submenu

Generator Configuration
The values in this menu are user-entered for the
generator set configuration and are NOT measured
values of the generator set.
Note: Have
setup
Decision-Makerr 3500 controller performed only
by an authorized Kohler distributor/dealer. The
setup and adjustments are password protected.
Operating Mode displays the programmer
D
entered generator set application configuration as
Standby or Prime.
Application Type displays the programmer
D
entered generator set application type as None,
Marine, Mobile, Standby or Prime.
System
Voltage
D
programmer-entered L1-L2-L3 output voltage for
three-phase or the L1-L2 output voltage for
single-phase.
System
Frequency
D
programmer-entered L1-L2-L3 output voltage
frequency for three-phase or the L1-L2 output
voltage frequency for single-phase.
System Phase displays the programmer-entered
D
configuration as Single Phase, Single Phase
Dogleg, Three Phase Wye, or Three Phase Delta.
Rated Engine Speed displays the programmer
D
entered engine speed in RPM.
Adjusted Engine RPM displays the target engine
D
speed setting.
kW Rating displays the programmer entered kW
D
value for the generator set.
kVA Rating displays the programmer entered kVA
D
value for the generator set.
Rated Current displays the programmer entered
D
current value for the generator set.
Battery Voltage displays the programmer entered
D
battery voltage.
and
adjustments
of
displays
displays
Section 1 Specifications
the
the
the
23