Corrective Action Replace heater(s) if defective. See Evaporator Heater Removal and
Component Contactor
Troubleshooting Check voltage at heater contactor on the heater side.
Corrective Action If no voltage present, replace heater contactor if defective.
AL62
O2 Out of Range
Cause: This is a notification alarm and does not pose a risk to fresh produce. It is triggered when there is an
indication that O2 level is rising after reaching its setpoint (+ 1%). If O2 level exceeds 4% above setpoint,
the alarm is activated. The alarm does not activate if the unit was pre-tripped or trip started between last
reaching its O2 setpoint and exceeding the plus 4%, or if power has been turned off for eight hours. The
alarm is deactivated if O2 drops below setpoint (+ 1%) or if a Pre-Trip or Trip Start is performed.
Component Scrubber Failure
Troubleshooting See the troubleshooting of the Scrubber Motor in the AL29 alarm.
Component XtendFRESH Solenoid Valves
Troubleshooting See the troubleshooting of the Solenoid Air Vent in the AL29 alarm.
Component Container Air Tightness
Troubleshooting Seal container where possible (access panels, rear doors, mounting hardware,
AL63
Current Limit
Cause: Unit operating above current limit.
Component Refrigeration System
Troubleshooting Check unit for air flow restrictions.
Corrective Action Clean or remove any debris from coils.
Troubleshooting Check unit for proper operation.
Corrective Action Repair as needed.
Component Power supply
Troubleshooting Confirm supply voltage/frequency is within specification and balanced according
Corrective Action Correct power supply.
Component Current limit set too low
Troubleshooting Check current limit setting Code Cd32.
Corrective Action The current limit can be raised (maximum of 23 amps) using Cd32.
AL64
Discharge Temperature Sensor (CPDS)
Cause: Compressor Discharge Temperature Sensor (CPDS) out of range.
Component Compressor Discharge Temperature Sensor (CPDS).
Troubleshooting Test the CPDS. See Sensor Checkout Procedure,
Corrective Action Replace the CPDS if defective. See Sensor Replacement
Table 4–5 Alarm Indications and Descriptions
Replacement
Section
7.16.
etc).
Section
to Electrical Data
4–39
3.3.
Section
7.29.2.
Section
7.29.
T-362