Carrier PrimeLINE Operation And Service Manual page 71

Container refrigeration units
Table of Contents

Advertisement

AL08
High Compressor Pressure Ratio
Cause: Controller detects discharge pressure to suction pressure ratio is too high.
The controller will attempt to correct the situation by restarting the compressor.
Component Discharge Pressure Transducer (DPT)
Troubleshooting Confirm accurate DPT pressure readings. See Manifold Gauge Set
Corrective Action Replace DPT if defective.
AL09
O2 Sensor Failure
Cause: Triggered anytime the O
was detected.
Component O
Troubleshooting Check Cd44 and scroll down to 02V. The O
AL10
CO2 Sensor Failure
Cause: Triggered anytime the CO
was detected.
Component CO
Troubleshooting Check the voltage at MC5 to the ground pin on TP9 (1 - 4.7 vdc).
Corrective Action The alarm is triggered off when voltage is within operating range.
AL14
Phase Sequence Detect Fault
Cause: Controller is unable to determine the correct phase relationship.
Component N/A
Troubleshooting Power cycle the unit.
Corrective Action Resetting the unit may correct problem, monitor the unit.
Component Wiring
Table 4–5 Alarm Indications and Descriptions
sensor reading is outside of the normal operation range, after an initial signal
2
Sensor, O
Amplifier, Sensor Switch Module (if equipped)
2
2
millivolts (130mV to 4100mV).
Switch equipped: If voltage is not present at Cd44 and a sensor switch module is
installed, check for O
voltage on the black wire connected to the sensor switch
2
module, connecting ground of meter to TP9. If the voltage is in the 130mV to 4.1V
range, directly wire the black wire to KD04. This may cause an AL07 depending
on O
reading but XtendFRESH will operate normally. If no voltage on the black
2
wire, proceed to next step.
Check wiring (see schematic), and correct if found mis-wired.
If O
sensor is available, remove the upper fresh air panel and evaporator motor
2
and replace the sensor. If after replacing sensor AL09 continues, replace
amplifier.
If parts are not available, turn XtendFRESH option off at code Cd43 and open the
Manual Fresh Air Vent.
sensor reading is outside of the normal operation range, after an initial signal
2
Sensor
2
Check wiring (see schematic), and correct if found mis-wired.
If part is available, remove upper fresh air panel and evaporator motor; replace
sensor. If no part is available, take no action and service at next PTI.
XtendFRESH will continuously run the scrubber. O2 level will be controlled with
the opening and closing of the fresh air vents as required.
4–31
Section
sensor output will be displayed in
2
7.2.
T-362