5.5 Connect Remote Monitoring Receptacle

If remote monitoring is required, connect the remote monitor plug at the unit receptacle (see
When the remote monitor plug is connected to the remote monitoring receptacle, the following remote circuits are
energized:
Sockets B to A: Energizes remote cool light
Sockets C to A: Energizes remote defrost light
Sockets D to A: Energizes remote in-range light

5.6 Starting and Stopping Instructions

Make sure that the unit circuit breaker(s) CB-1 & CB-2 and the Start-Stop switch (ST) are in the
"O" (OFF) position before connecting to any electrical power source.
The electronic phase detection system will check for proper compressor rotation within the first 30 sec-
onds. If rotation is not correct, the compressor will be stopped and restarted in the opposite direction.
If the compressor is producing unusually loud and continuous noise after the first 30 seconds of oper-
ation, stop the unit and investigate.
5.6.1

Starting the Unit

1. Verify that power is properly applied, the fresh air vent is in proper position, and (if required) the water-
cooled condenser is connected.
2. Place the Start-Stop switch (ST) to position "I" (ON) (see
container ID (Cd40), software version (Cd18) and unit model number (Cd20) will be displayed in sequence.
3. Continue with the Start Up Inspection. See
5.6.2

Stopping the Unit

1. To stop the unit, place the Start-Stop switch (ST) in position "0" (OFF).

5.7 Start-Up Inspection

5.7.1

Physical Inspection

Check rotation of condenser fan and evaporator fans.
5.7.2

Check Controller Function Codes

Check, and if required, adjust controller function codes (Cd27 through Cd37) in accordance with desired operating
parameters. See
Table
4–4.
5.7.3

Start Temperature Recorder

1. Check and, if required, set the DataCORDER Configuration in accordance with desired recording
parameter. See
Section
2. Enter a "Trip Start" with the following instructions:
a. Press the ALT MODE key. When the left display shows "dC", press the ENTER key.
b. Scroll to code dC30.
c. Press and hold the ENTER key for five seconds.
d. The "Trip Start" event will be entered in the DataCORDER.
5.7.4

Complete Inspection

Allow the unit to run for five minutes to stabilize conditions, and then perform a pre-trip diagnosis in accordance
with
Section
5.8.
WARNING
!
NOTE
Section
.
5–5
Figure
3.10). The controller function codes for the
5.7.
Figure
3.10).