Troubleshooting Check unit wiring.
Corrective Action Correct wiring.
Component Current Sensor
Troubleshooting Check the right-most digit in display at code Cd41.
Corrective Action Replace current sensor if defective.
AL16
Compressor Current High
Cause: Compressor current draw is over the calculated maximum for 10 minutes.
Component Current Sensor
Troubleshooting Compare value at code Cd03 to actual measured current at wire T1-T2 or T3
Corrective Action Replace current sensor if defective.
Component Amperage is indeed too high.
Troubleshooting Confirm supply voltage / frequency is within specification and balanced
Corrective Action Correct power supply.
Component Operating Conditions
Troubleshooting Make sure system pressures are relevant to operating conditions.
Corrective Action Check air flow of condenser.
Component Monitor Unit
Troubleshooting Alarm is display only the alarm may clear itself during operation.
Corrective Action If alarm remains active or is repetitive replace compressor at next available
AL17
Compressor Pressure Delta Fault
Cause: Compressor has attempted to start in both directions and fails to generate sufficient pressure differential
between SPT and DPT.
Component N/A
Troubleshooting Controller will attempt to restart every 20 minutes and deactivate the alarm if
Corrective Action Resume normal operation.
Component Discharge Pressure Transducer (DPT)
Troubleshooting Confirm accurate DPT pressure readings. See Manifold Gauge Set
Corrective Action Replace DPT if defective.
Component Suction Pressure Transducer (SPT)
Troubleshooting Confirm accurate SPT pressure readings. See Manifold Gauge Set
Corrective Action Replace SPT if defective.
T-362
Table 4–5 Alarm Indications and Descriptions
Confirm pressure readings during start-up; suction pressure should decrease
and discharge pressure should increase.
If display is 3 or 4, check compressor / sensor wiring.
If display is 5, the current sensor is defective.
going to the compressor contactor. If there is a difference, determine whether this
is caused by current sensor or amp clamp tool.
according to Electrical Data
Check Refrigerant charge. See Refrigeration System Service
opportunity. See Compressor Service
successful.
4–32
Section
3.3.
Section
7.9.
Section
7.3.
Section
7.2.
Section
7.2.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Primeline one69nt40-561-20069nt40-561-50069nt40-565-20069nt40-565-500

Table of Contents