Cable Type
Battery cable
NOTE
● The data in the table is applicable when the ambient temperature is 30°C (in air) and cables are in a single
loop.
● When the ambient temperature is not 30°C or cables in multiple loops are routed together, use cables with
larger cross-sectional areas if the cabling distance is long.
● Battery cables should be able to withstand a temperature of at least 90°C.

4.1.2 Tools

Use tools with insulated handles. The following table is for reference only.
Table 4-2 Installation tools and instruments
Issue 04 (2021-01-05)
Maximum
Current (A)
40
50
63
80
100
100
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Minimum Cross-
Sectional Area
2
(mm
)
6
10
10
10
16
16
4 Installation
Maximum Cross-
Sectional Area
2
(mm
)
16
16
16
35
35
35
35