Figure 6-7 Configuring IO ports
Setting Alarm Actions for Dry Contact Outputs
You can set alarm actions for dry contact outputs based on site requirements. The
initial status is as follows: When an alarm is generated, dry contacts are closed;
when no alarm is generated, dry contacts are open.
Figure 6-8 Setting alarm actions for dry contact outputs
Setting Alarm Conditions for Dry Contact Inputs
You can set alarm conditions for dry contact inputs based on site requirements.
For example, if DIN1 Alarm Condition is set to Close, the SMU generates a DIN1
Alarm for dry contact input DIN1 when it is closed.
Issue 04 (2021-01-05)
Copyright © Huawei Technologies Co., Ltd.