Huawei ETP4860-B1A2 User Manual page 82

Embedded power
Table of Contents

Advertisement

ETP4860-B1A2 Embedded Power
User Manual
and output current as well as battery connection/disconnection and equalized/
float charge.
Path: Site Configuration > Power System > Basic Control > System Control
Mode
Deleting the Rectifiers Failing in Communication
After you remove one or more rectifiers, the SMU generates a Communication
Failed alarm. If you confirm that the rectifiers will not be reinstalled, manually
delete the information about the removed rectifiers.
Path: Site Configuration > Rectifier Group > Basic Control > Delete Rectifier
Failed in Communication
Collecting Rectifier Fault Information
If rectifier alarms cannot be cleared according to Rectifying Common Faults,
Collect Fault Info can be performed to export rectifier data, which can be
provided to Huawei technicians for rectifier fault diagnosis.
Path: Site Configuration > Rectifier Group > Basic Control > Collect Fault Info
Switching Between Equalized and Float Charge for Lead-Acid Batteries
Path: Site Configuration > Battery Group > Basic Control > Charge Control
Connecting and Disconnecting the Lead-Acid Battery Supply
If the AC or DC power supply fails after you disconnect the battery supply, all
loads will be powered off. Therefore, exercise caution with this operation.
You can manually connect or disconnect the battery supply when the system
works in manual control mode.
Path: Site Configuration > Battery Group > Basic Control > BLVD Control
Exporting Historical Alarms, and Battery Test Records
You can export historical alarms, and battery test records on the LIVE-C APP to
quickly collect information and locate system faults.
Path: OM Tool > Data Download
Issue 04 (2021-01-05)
You can manually switch between equalized charge and float charge when
the system works in manual control mode.
Batteries keep in boost charge state after boost charge is manually started.
When the float charge conditions are met (for example, time for boost charge
expires), the batteries automatically switch to the float charge state.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
7 Maintenance
75

Hide quick links:

Advertisement

Table of Contents
loading