Expansion Setting Parameters - Omron CJ Series Operation Manual

Machine automation controller analog i/o units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

3 Isolated-type Universal Input Units
3-2-9
Expansion Setting Parameters (User-defined Variables:
_sCJPH41U_Ex_Param Type)
Member name
Setting Parameter Group 3: Continuously Refreshed Parameters (parameters that can be changed regardless of the CPU Unit
mode)
Process value alarm settings
Ch#_PVAlmValCfg_HH
Ch#_PVAlmValCfg_LL
Rate-of-change value alarm settings
Ch#_RateAlmValCfg_H
Ch#_RateAlmValCfg_L
Setting Parameter Group 4: Initial Settings Parameters (Parameters that are changed when the Controller is reset or the Unit
is restarted)
Setting of Expansion Operation Data
ExtIOArea
ExtIOAdr
Platinum Resistance thermometer input compensation function
RTDCompensate
WORD
Cold junction compensation method settings
CJCompensate
WORD
Square root calculation function
Ch#_SqrtCfg
WORD
Rate-of-change measurement function
Ch#_InRateSpanValCfg_H
Ch#_InRateSpanValCfg_L
Ch#_RateCmpIntvlTm
Ch#_RateCmpUnit
3-30
Type
R/W
Data range
DINT
RW
−2147483648 to
+2147483647
DINT
RW
−2147483648 to
+2147483647
DINT
RW
−2147483648 to
+2147483647
DINT
RW
−2147483648 to
+2147483647
UINT
RW
0 to 5
UINT
RW
0 to 32767
RW
16#00 to 16#0F
RW
16#0000 or 16#0001
RW
16#0000 or 16#0001
INT
RW
−32000 to +32000
INT
RW
−32000 to +32000
USINT
RW
1 to 16
BYTE
RW
16#00 or 16#01
CJ-series Analog I/O Units Operation Manual for NJ-series CPU Unit(W498)
Default
Parameter contents
+42000
Process Value HH (high high limit) Alarm Setting
(Set at process value scaling value.)
−2000
Process Value LL (low low limit) Alarm Setting
(Set at process value scaling value.)
+40000
Rate-of-change Value H (high limit) Alarm Set-
ting
(Set at rate-of-change scaling value.)
0
Rate-of-change value L (low limit) Alarm Setting
(Set at rate-of-change scaling value.)
---
Area of Expansion Operation Data
0: Not used; 1: DM Area; 2: CIO Area;
3: Work Area; 4: Holding Area;
5: EM Area bank 0
---
First Word in Expansion Operation Data Area
16#00
Temperature resistance thermometer input com-
pensation setting
Bit 00: Input No. 1, Bit 01: Input No. 2, Bit 02:
Input No. 3, Bit 03: Input No. 4
0: Disable
1: Enable
16#0000
Cold Junction Compensation Method for Ther-
mocouple Input
16#0000: Internal (Uses Unit's Cold Junction
sensor)
16#0001: External (Does not use Unit's Cold
Junction sensor)
16#0000
Square Root Extraction
(when maximum scaling value > minimum scal-
ing value)
16#0000: Disable
16#0001: Enable
+10000
Maximum Rate-of-change Range Value (setting
scaling value/comparison time interval)
−10000
Minimum Rate-of-change Range Value (setting
scaling value/comparison time interval)
1
Rate-of-change Comparison Time Interval
16#00
Rate-of-change Comparison Time Interval Unit
16#00: s
16#01: Conversion time