Omron CJ Series Operation Manual page 96

Machine automation controller analog i/o units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

2 Isolated-type Direct Current Input Unit
Device variable (name)
(1 or 2 is included in
place of #.)
*_Ch#_PVSclValCfg_H
*_Ch#_PVSclValCfg_L
Square root calculation function
*_Ch#_SqrtCfg
WORD
Mean value processing function
*_Ch#_AveCfg
Advanced alarm functions
*_Ch#_AlmHystrsValCfg
*_Ch#_AlmOnDelayTmCfg
Rate-of-change measurement function
*_Ch#_InRateSpanValCfg_H
*_Ch#_InRateSpanValCfg_L
*_Ch#_RateSclValCfg_H
*_Ch#_RateSclValCfg_L
*_Ch#_RateCmpIntvlTm
Expansion Setting Parameter settings
*_ExtMemArea
*_ExtMemAdr
Parameter status
*_Ch#_CfgErrAdr
Note 1 The ERC indicator on the Unit's front panel will light if an out-of-range setting is made in Set-
ting Parameter Group 1 (Continuously Refreshed Parameters), Setting Parameter Group 2
(Initial Settings Parameters), or the Expansion Setting Parameters.
The offset (the number of words) from the start address to the lowest memory address that
has the range error will be stored in the Address of Data Range Error.
If the lowest memory address that has the range error is an Expansion Setting Parameter, the
offset value shown in the Address of Data Range Error will be 100 or greater. (The value will
be 100 if the first word of the Expansion Setting Parameters is erroneous.)
For the correspondence between range error addresses and setting parameter or expansion
setting parameter addresses, refer to A-3 Correspondence Table of Analog I/O Unit Variables
and CJ-series CPU Addresses. "m" in the table indicates the first word allocated in DM. m =
D20000 + (N × 100) (N: Unit number)
2 When specifying Expansion Setting Parameters, be sure that the area does not overlap with
other areas that are in use.
If areas overlap, the memory may be overwritten and unexpected operation may occur.
2-8
Type
R/W
Data range
−32000 to +32000
INT
RW
−32000 to +32000
INT
RW
RW
16#0000/16#0001
UINT
RW
1 to 128
UINT
RW
0 to 32000
UINT
RW
0 to 60
−32000 to +32000
INT
RW
−32000 to +32000
INT
RW
−32000 to +32000
INT
RW
−32000 to +32000
INT
RW
UINT
RW
1 to 16
UINT
RW
0 to 5
UINT
RW
0 to 32767
UINT
R
0 to 63
CJ-series Analog I/O Units Operation Manual for NJ-series CPU Unit(W498)
Default
Parameter contents
+4000
Scaling Value for Maximum Value in Range
(Span)
0
Scaling Value for Minimum Value in Range
(Zero)
16#0000
Square Root Extraction
(only enabled when maximum scaling value >
minimum scaling value)
16#0000: Disable
16#0001: Enable
25
Number of Values for Calculating Moving Aver-
age for Mean Value Processing
40
Alarm Hysteresis Settings (Shared with process
value alarm and rate-of-change alarm.)
(Set at process value scaling value.)
0
Alarm ON-delay Time (Shared with process
value alarm and rate-of-change alarm.)
Unit: s
+4000
Maximum Rate-of-change Range Value (Setting
scaling value/comparison time interval)
−4000
Minimum Rate-of-change Range Value (Setting
scaling value/comparison time interval)
+4000
Scaling Value for Maximum Rate-of-change
Range Value
−4000
Scaling Value for Minimum Rate-of-change
Range Value
1
Rate-of-change Comparison Time Interval
Unit: s
---
Area of Expansion Setting Parameter
0: Not used; 1: DM Area; 2: CIO Area;
3: Work Area; 4: Holding Area;
5: EM Area bank 0
---
First Word in Expansion Setting Parameters
Area
0
Address of Data Range Error