Omron CJ Series Operation Manual page 113

Machine automation controller analog i/o units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Device variable
Type
(name)
Input Signal Type
*_Ch#_SensTypCfg
UINT
Advanced alarm functions
*_Ch#_AlmHystrsValCfg
UINT
*_Ch#_AlmOnDelayTmCfg
UINT
Process value scaling
*_Ch#_PVSclValCfg_H
INT
*_Ch#_PVSclValCfg_L
INT
Expansion Operation Data allocation settings *2
*_ExtIOCfg
WORD
*_ExtIOAdr
UINT
Parameter status
*_CfgErrAdr
UINT
*1 The ERC indicator on the Unit's front panel will light if an out-of-range setting is made in either Setting Param-
eter Group 1 (Continuously Refreshed Parameters) or Setting Parameter Group 2 (Initial Settings Parameters).
The offset (the number of words) from the start address to the lowest memory address that has the range error
will be stored in the Address of Data Range Error.
For the correspondence between range error addresses and setting parameter addresses, refer to A-3 Corre-
spondence Table of Analog I/O Unit Variables and CJ-series CPU Addresses. "m" in the table indicates the
First Word allocated in DM. m = D20000 + (N × 100) (N: Unit number)
*2 When specifying Expansion Operation Data, be sure that the area does not overlap with other areas that are in
use.
If areas overlap, the memory may be overwritten and unexpected operation may occur.
CJ-series Analog I/O Units Operation Manual for NJ-series CPU Unit(W498)
R/W
Data range
Default
RW
0 to 54
RW
0 to 9999
RW
0 to 60
−32000 to +32000
RW
+4000
−32000 to +32000
RW
RW
16#0000 or
16#0000 Expansion Operation Data Setting
16#0001
RW
0 to 6143
R
0 to 40
3 Isolated-type Universal Input Units
Parameter contents
54
0: RTD-Pt100
21: TC-K
3: RTD-JPt100
23: TC-J
7: RTD-Pt1000
25: TC-T
33: TC-L
36: TC-R
37: TC-S
38: TC-B
0
Alarm Hysteresis
• Temperature input: Set value × 0.1 °C, or 0.1 °F
• Voltage or current input: Set value × 1 digit
0
Alarm ON-delay Time
Unit: s
Scaling Value for Maximum Value in Range (Span)
0
Scaling Value for Minimum Value in Range (Zero)
0: Not used, 1: Used
0
First Word in Expansion Operation Data Area
In the Expansion Operation Data, the same data as
PVAlmSta is output.
0
Address of Data Range Error
48: 4 to 20mA
49: 0 to 20mA
50: 1 to 5V
53: 0 to 5V
54: 0 to 10V
3
3-9