Specifications - Omron CJ Series Operation Manual

Machine automation controller analog i/o units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

2-1-6

Specifications

Item
Model
Applicable PLC
Unit classification
Mounting position
Maximum number of Units
Unit numbers
Areas for data
Operation Data
exchange
Setting Parame-
ters *1
Expansion Opera-
tion Data
Expansion Setting
Parameters *1
Number of inputs
Input signal type
Scaling
Process data
Accuracy (25°C)
Temperature coefficient
Resolution
Input signal range
Maximum input rating
Input impedance
Response time
Warmup time
Conversion cycle
CJ-series Analog I/O Units Operation Manual for NJ-series CPU Unit(W498)
CJ1W-PDC15
NJ Series
CJ-series Special I/O Unit
NJ-series CPU Rack, Expansion Rack
40 (within the allowable current consumption and power consumption range)
00 to 95 (Cannot duplicate Special I/O Unit numbers.)
10 words/Unit (device variables for CJ-series Unit)
Direct Current Input Unit to CPU Unit:
All process values, process value alarms (LL, L, H, HH), rate-of-change values, rate-of-change
alarms (L, H), disconnection alarms, cold junction sensor errors, adjustment period end/notice.
100 words/Unit (device variables for CJ-series Unit)
CPU Unit to Direct Current Input Unit:
Input types, input range (user setting), process value scaling, rate-of-change input range, rate-of-
change value scaling, number of items for moving average, process value alarm setting (LL, L, H,
HH), rate-of-change alarm setting (L, H), zero/span adjustment value, square root calculation func-
tion, Expansion Setting Parameters settings.
35 words/Unit (user-defined variables: _sCJPDC15_Ex_CmdSta type)
CPU Unit to Direct Current Input Unit:
Bits for beginning or resetting the hold function selection, adjustment period control, control bits
Direct Current Input Unit to CPU Unit:
Adjustment period notices, peak and bottom values, top and valley values, integral values
46 words/Unit (user-defined variables: _sCJPDC15_Ex_Param type)
CPU Unit to Direct Current Input Unit:
Expansion Operation Data settings, adjustment period control, peak and bottom detection, top and
valley detection, integral value calculation
2
4 to 20 mA, 0 to 20 mA, 0 to 10 V, −10 to 10 V, 0 to 5 V, −5 to 5 V, 1 to 5 V, 0 to 1.25 V, −1.25 to 1.25
V (separate for each input), and ±10-V user-set range (specified range within –10.000 V to 10.000
V)
It is possible to scale process data. (Any minimum and maximum values can be set.) (2 inputs set
separately.)
Data can be converted at 0% to 100%.
The value derived from carrying out the following processing in order of the actual process data in
the input range is output as a 16-bit integer (INT).
1) Mean value processing → 2) Scaling → 3) Zero/span adjustment → 4) Square root calculation
→ 5) Output limits
±0.05%
±0.008%/°C
1/64,000
For 4 to 20 mA, 0 to 20 mA, 0 to 10 V, 0 to 5 V, 1 to 5 V, 0 to 1.25 V inputs:
−15 to 115%
For −10 to 10 V, −5 to 5 V, −1.25 to 1.25 V inputs:
−7.5 to 107.5%
Voltage: ±15 V
Current: ±30 mA
For current inputs: 250 Ω (typical)
For voltage inputs: 1 MΩ min.
100 ms max. (travel time from input 0% to 90%, for ±10 V step input and with moving average for 4
samples)
10 min
10 ms/2 inputs