Toshiba nv Series Instruction Manual page 39

Unified controller
Hide thumbs Also See for nv Series:
Table of Contents

Advertisement

When the registration above is complete, check that the
network information of the corresponding EN811 module can
be read from the serial communication port (TOOL).
From the product tree, open the module parameter screen for the
EN811 module previously registered.
Figure 3-8
Register the IP address type, IP address, and subnet mask.
Note
• Be careful so that the address does not overlap with other nodes.
Individual settings are as follows.
For the IP address type, select from Class B, Class C, and Arbitrary.
Class B sets all of the bits No.6 to 8 of the operation mode setting
switches (MODE) of the EN811 module to OFF.
IP address : 172.16.64.xx (xx indicates the value of the station
address setting switches)
Subnet mask : 255.255.192.0
Module parameter registration screen
Unified Controller nv series Ethernet (EN811) Module Operation Manual
3.3 Setting with the engineering tool
25