Service - HART mode
Service - Copy sensor
data
VEGASON 61 • Four-wire 4 ... 20 mA/HART
6 Set up with the display and adjustment module PLICSCOM
The activation of SIL has the following impact:
In the menu item " Failure mode" under " Current output", the
parameters " Hold value" and " 20.5 mA" are blocked
In the menu item " HART mode", the function " Multidrop" is
blocked
Note:
For such applications, it is absolutely necessary to take note of "
Safety Manual".
HART offers standard and multidrop mode.
The mode "standard" with the fixed address 0 means outputting the
measured value as a 4 ... 20 mA signal.
In Multidrop mode, up to 15 sensors can be operated on one two-wire
cable. An address between 1 and 15 must be assigned to each sen-
sor.
8)
In this menu item you determine the HART mode and enter the ad-
dress for multidrop.
HART mode
Standard
Address 0
The default setting is standard with address 0.
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the display
and adjustment module. A description of the function is available in
the operating instructions manual " Display and adjustment module".
The following data are read out or written with this function:
Measured value presentation
Adjustment
Medium
Vessel shape
Damping
Linearisation curve
Sensor-TAG
Displayed value
Display unit
Scaling
Current output
Unit of measurement
Language
The following safety-relevant data are not read out or written:
HART mode
PIN
The 4 ... 20 mA signal of the sensor is switched off. The sensor uses a
8)
constant current of 4 mA. The measuring signal is transmitted exclusively as
a digital HART signal.