Service - Reset
VEGASON 61 • Four-wire 4 ... 20 mA/HART
6 Set up with the display and adjustment module PLICSCOM
Percent
Current
Pressure (with pressure transmitters)
Distance (with radar and guided radar (GWR))
With Profibus PA sensors, the selection of the simulated value is
made via the "Channel" in the menu " Basic adjustments".
How to start the simulation:
1. Push [OK]
2. Select the requested simulation variable with [->] and confirm
with [OK].
3. Set the requested numerical value with [+] and [->].
4. Push [OK]
The simulation is now running, with 4 ... 20 mA/HART a current is
output and with Profibus PA or Foundation Fieldbus a digital value.
How to interrupt the simulation:
Push [ESC]
Information:
The simulation is automatically terminated 10 minutes after the last
pressing of a key.
Simulation
Start simulation?
If the function " Reset" is carried out, the sensor resets the values of
the following menu items to the reset values (see table):
Function
Max. adjustment
Min. adjustment
Medium
Vessel shape
Damping
Linearisation
Sensor-TAG
Displayed value
Current output - characteristics
Current output - max. current
Current output - min. current
Current output - failure
Sensor-specific basic adjustment.
4)
Depending on the sensor type, see chapter "Technical data".
5)
Depending on the sensor type, see chapter "Technical data".
6)
Reset value
Final value blocking distance in m(d)
Meas. range end in m(d)
Liquid
not known
0 s
Linear
Sensor
Distance
4 ... 20 mA
20.5 mA
3.8 mA
< 3.6 mA
4)
5)
6)
35