6 Set up with the display and adjustment module PLICSCOM
Basic adjustment - Min.
adjustment
28
Fig. 25: Parameterisation example, Min./max. adjustment
1
Min. level = max. distance (depending on the sensor)
2 Max. level = min. distance (final value of the blocking distance, depending
on the sensor)
3
Reference plane
The actual product level during this adjustment is not important,
because the min./max. adjustment is always carried out without
changing the product level. These settings can be made ahead of
time without the instrument having to be installed.
Proceed as follows:
1. Move from the measured value display to the main menu by
pushing [OK].
Basic adjustment
Display
Diagnostics
Service
Info
2. Select the menu item " Basic adjustment" with [->] and confirm
with [OK]. Now the menu item " Min. adjustment" is displayed.
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3. Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
4. Enter the distance value in m for empty vessel (e.g. distance from
the sensor to the vessel bottom) corresponding to the percentage
value.
VEGASON 61 • Four-wire 4 ... 20 mA/HART
3
100%
2
1
0%