Commissioning
!
DIP switch
A
B
A
Standard
A
* The red LED flashes if there is a fault that you can correct.
** The red LED lights up continuously if the device has a fault that cannot be corrected. See also Page 78,
"Troubleshooting".
*** Flashes at 5-second intervals.
!
72
6.3
Commissioning with electronic inserts
FEI53 or FEI57S
This chapter describes the process for commissioning the device with electronic insert versions
FEI53 and FEI57S.
Note!
The measuring system is not operational until you have carried out a calibration at the switching
unit.
For information on how to carry out the calibration, refer to the documentation for the Nivotester
switching device FTCxxx.
6.3.1
Setting the alarm response if the measuring range is exceeded
A A
1 1
FEI5x
FEI5x
Standard
- -
+ +
Function
Standard: If the measuring range is exceeded no alarm is output (factory
setting).
: If the measuring range is exceeded an alarm is output.
Note!
• With this setting, you can determine the alarm response of the measuring system If the measuring
range is exceeded. You can switch the alarm on or off If the measuring range is exceeded.
• All other settings with regard to the alarm response have to be configured on the respective
Nivotester switching device.
B B
2 2
0...1600pF
0.....500pF
Liquicap M FTI51, FTI52
LED
LED
on
on
flashing
flashing
of off f
Light emitting diodes (LED signals)
1 (green)
2 (red)*/**
Operational
Fault
Flashes***
Off
Flashes***
Off
Endress+Hauser
BA300Fen016