Commissioning
!
!
58
6.3
Commissioning with electronic inserts
FEI53 or FEI57S
This chapter describes the process for commissioning the device with electronic insert
versions FEI53 and FEI57S.
Note!
The measuring system is not operational until you have carried out a calibration at the
switching unit.
For information on how to carry out the calibration, refer to the documentation for the
Nivotester switching device: FTC325 3-Wire, FTC325 PFM, FTC625, FTC325, FTC470Z or
FTC471Z
A A
1 1
FEI5x
FEI5x
Standard
- -
+ +
LED 1 operational
: Flashes at 5-second intervals.
LED 2 fault
: The red LED flashes if there is a fault that you can correct.
LED 2 fault
: The red LED lights up continuously if the device has a fault that cannot be corrected. See also
Page 67, "Troubleshooting".
6.3.1
Setting the alarm response if the measuring range is exceeded
DIP switch
A
B
A
Standard
A
Note!
• With this setting, you can determine the alarm response of the measuring system If the
measuring range is exceeded. You can switch the alarm on or off If the measuring range is
exceeded.
• All other settings with regard to the alarm response have to be configured on the
respective Nivotester switching device.
B B
2 2
0...1600pF
0.....500pF
Function
Standard: If the measuring range is exceeded no alarm is output (factory
setting).
: If the measuring range is exceeded an alarm is output.
Liquicap M FTI51, FTI52
LED
LED
on
on
flashing
flashing
of off f
Endress+Hauser
BA300Fen016