ly start after power up.
RST TIME
10 SEC
S S S S Unload Stop Timer -- If the machine is run-
ning in AUTO mode, this parameter speci-
fies the amount of time that the machine will
run unloaded before shutting off. If the time
is set less than 15 minutes (five minutes, for
example), there may be times when the ma-
chine will run unloaded for more than five
minutes. This is because there is another
timer that keeps the machine from being
started more than four times an hour.
UNLD TIM
15 MIN
S S S S Language select -- English, German,
Spanish, Italian and French may be se-
lected for display language.
LANGUAGE
ENGLISH
S S S S Units -- English or metric units may be se-
lected.
UNITS
ENGLISH
S S S S Communications ID # -- This is the net-
work address of a machine. If there is more
than one machine connected to the net-
work, each machine must have a unique
number.
COM ID #
S S S S Communications Baud Rate -- This
should always be selected to 9600 baud for
all sequencing modes. It may be lower for
slave or monitoring modes.
BAUDRATE
9600
6.4 DELUXE PARAMETER SETUP
The following parameters are only available on de-
luxe model Supervisor II.
S S S S Sequence Method -- This parameter sets
the method used for sequencing. The
choices
are
SLAVE, HOURS, COM ID#. See the Se-
1
DISABLED,
REMOTE,
COMPRESSOR OPERATION
quencing
&
02250057--696) for details about these
modes.
SEQUENCE
HOURS
S S S S Drain Interval -- The time between actua-
tion of the drain valve.
DRN INTV
10 MIN
S S S S Drain Time -- The amount of time that the
drain valve is actuated.
DRN TIM
1 SEC
S S S S Last Communication Number -- Used
only for sequencing, see Sequencing &
Protocol Manual for details.
LAST COM
S S S S Lowest Allowable Pressure -- Used only
for sequencing, see Sequencing & Protocol
Manual for details.
LOWEST
90 PSI
S S S S Recovery Time -- Used only for sequenc-
ing, see Sequencing & Protocol Manual for
details.
RECOVER
10 SEC
S S S S Rotate Time -- Used only for sequencing,
see Sequencing & Protocol Manual for de-
tails.
ROTATE
S S S S Machine Capacity -- Used only for se-
quencing, see Sequencing & Protocol
Manual for details.
CAPACITY
S S S S Sequence Hours -- Used only for se-
quencing, see Sequencing & Protocol
Section 6
Protocol
Manual
(P/N
3
50
100
25