Sullair LS-20 Operator's Manual And Parts List page 15

Industrial air compressor
Hide thumbs Also See for LS-20:
Table of Contents

Advertisement

4.1 BASIC INTRODUCTION
Ref er t o
F igur e 4 --
1. T he S uper v is or I I has a t wo line
display to show temperature, pressure and status. It
has a keypad for operating the compressor, pro-
gramming the control points and selecting displays.
There is a graphic illustration with lamps that light to
show the item being displayed. The lamps flash if
that component is in an alarm condition.
4.2 KEYPAD- -ALL MODELS
The keypad is used to control the machine as well as
dis play s t at us and c hange s et point s . Ref er t o
4 -- 1
f or f ollowing k ey des c r ipt ions .
S S S S Stop -- Used to put the machine into manu-
al stop. It is also used to clear alarm condi-
tions.
S S S S Continuous -- Starts machine if no alarm
conditions are present. Also used to clear
alarm conditions while machine is running.
S S S S Auto -- Starts machine and selects auto
mode if no alarm conditions are present.
Also used to clear alarm conditions while
machine is running.
S S S S Display -- Used to display pressures, tem-
peratures and other status information (See
section on STATUS DISPLAYS).
DISPLY
S S S S Logo -- Used for various functions de-
scribed in later sections.
S S S S Program -- Used to enter the parameter
change mode where control parameters
may be displayed and changed (See PA-
RAMETER SETUP).
PROG
S S S S Up arrow -- Used in status displays to
O
I
SUPERVISOR II DESCRIPTION
change displays and in parameter setup
mode to increment a value.
S S S S Down arrow, lamp test -- Used in status
displays to change displays and in parame-
ter setup mode to increment a value. When
in the default display the key will light all the
lamps for three seconds.
f igur e
4.3 STATUS DISPLAYS
By default the line pressure (P2) and discharge tem-
perature (T1) are shown on the bottom line of the
display, and machine status on the top line.
The following are the various machine status mes-
sages that indicate the state of the compressor:
(Display graphics shown below.)
S S S S STOP -- Compressor is off.
S S S S STANDBY -- Compressor is off but armed
to start. This state may be entered because
of a power up, or the unload timer had ex-
pired and stopped the machine. NOTE :
The machine may start at any time.
S S S S STARTING -- Machine is trying to start.
S S S S OFF LOAD -- Machine is running and off
loaded.
S S S S ON LOAD -- Machine is running and
loaded.
S S S S FULL LD -- Machine is running and fully
loaded. This state is only displayed if the
machine has a full load valve.
S S S S RMT STOP -- Compressor is off but armed
to start. The machine will start when the re-
mote start contact is closed. NOTE : the
machine may start at any time.
S S S S SEQ STOP -- Compressor is off but armed
to start. The machine will start when the se-
quencing conditions meet the criteria to
start. NOTE : the machine may start at any
time.
This default display appears as follows:
Section 4
STOP
110 180
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents