4.3 Install the Inverter

4.3.1 Mount on the wall:
• The inverters work optimally when the ambient temperature is not higher than 45°C.
• The installation height should preferably be parallel to the line of sight for easier operation and
maintenance.
• Keep the inverter installed away from flammable and explosive materials.
• Install the inverter in the place with a strong signal and no electromagnetic interference devices or
obstructions around.
• Keep the parameter labels and warning signs clear after installation.
• Avoid direct sunlight, rain, and snow.
Step 1: Mark position holes with the
mounting bracket, then drill holes with a
diameter of 13 mm and a depth of 65 mm in
the wall. The holes are shown below.
Step 3: Install handles or lifting rings on both sides of the inverter.
The handle is optional. Make sure the handle is securely fixed when installing the equipment.
Remove the handle and store it properly after installation.
Step 4: Install personnel can hold the handles or use lifting devices to hang the inverter on the
mounting bracket.
969mm
OB hole 12x18
Step 2: Fix the mounting bracket on the wall
with expansion screws. Customers have to
prepare the M10 expansion screws.
Expansion
Mounting bracket
tube
or
09
Screw

Advertisement