System/network setup screen—System, page 2 of 2 (large display only)
S813 IP Address—Contains the network address of the display. This address must be unique on the
network.
S814 Netmask— Netmask is used to divide IP addresses in subnet and specify the network available
to hosts.
S815 Gateway—Routes data and act as a proxy server or a fire wall when setting up networks.
S816 MAC—Unique hardware identifier of the Ethernet device. READ ONLY
S817 U2U Protocol—Always set to GBP.
S818 U2U Address—Unique identifier for each unit on the network. Display addresses range from
33 to 64. Each display on the U2U network must have a different U2U address.
S819 U2U Group—Used to create zones or groups within a U2U network. Once a group number is
selected the display will see only devices with the same group number. The group number can be
changed to view other devices in different groups.
S821 Bootloader Variables—Indicates if there has been a change to the bootloader since it was last
loaded, such as monitoring protocol, IP subnet setting, group or U2U number. This parameter should
only be activated by an authorized service person.
®
®