Table 12 Possible Event Settings-Events Listed May Vary By Specific Unit And Options Order - Emerson Liebert iCOM Manual

Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

Table 12
Possible event settings—events listed may vary by specific unit and options order
Event
FC LOCKOUT
COMPRESSOR(S) LOCKOUT
COMP 1 SHORT CYCLE
COMP 2 SHORT CYCLE
No Power
Condensate 1 Failure
Condensate 2 Failure
EC Fan Fault
HIGH SUP TEMP
LOW SUP TEMP
REDUCED ECO AIRFLOW
ECO HI TEMP OVERRIDE
TEMP CTRL SENSOR FAIL
HIGH DEW POINT
LOW DEW POINT
HI DEW POINT SENSOR A
LOW DEW POINT SENSOR A
HIGH REMOTE SENSOR
POWER "A" FAILURE
POWER "B" FAILURE
AIRFLOW SENSOR FAILURE
HUM CTRL SENSOR FAIL
LOSS OF FLOW
STAT PRES SENSOR FAIL
LOW STATIC PRESSURE
HIGH STATIC PRESSURE
STATPRES OUT OF RANGE
DAMPER FAILURE
BMS DISCONNECTED
Internal Delay
(Before Action Occurs)
2 Sec
2 Sec
0 Sec
0 Sec
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
59
Default Delay / Selectable
(Before Action Occurs)
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
0 - 9999
0 - 9999
0 seconds / 0-9999
5 seconds / 0-9999
5 seconds / 0-9999
10 seconds / 0-9999
30 seconds / 0-9999
30 seconds / 0-9999
3 seconds / 0-9999
10 seconds / 0-9999
3 seconds / 0-9999
30 seconds / 0-9999
30 seconds / 0-9999
30 seconds / 0-9999
30 seconds / 0-9999
30 seconds / 0-9999
10 seconds / 0-9999
10 seconds / 0-9999
10 seconds / 0-9999
30 seconds / 0-9999
5 seconds / 0-9999
120 seconds / 0-9999
120 seconds / 0-9999
120 seconds / 0-9999
150 seconds / 0-9999
10 seconds / 0-9999
ENABLED / DIS - ENAB
®
Liebert
iCOM
Operation
Type
(default)
WRN
WRN
MSG
MSG
WRN
WRN
WRN
ALM
WRN
ALM
WRN
WRN
ALM
WRN
WRN
WRN
WRN
WRN
ALM
ALM
WRN
WRN
ALM
ALM
WRN
WRN
WRN
ALM
WRN
®
for Liebert DSE