Figure 130 Sensor Calibration/Setup Screen - Emerson Liebert iCOM Manual

Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

Service Menu Parameters
S664 Results:—Read-only string that describes S665 through S668.
S665 DP Transducer Low—Shows the status of the low differential pressure transducer in both
inWC and Pa after it's setup at S659.
S666 DP Transducer High—Shows the status of the high differential pressure transducer in both
inWC and Pa after it's setup at S660.
S667 Actual DP Signal—Shows the actual differential pressure transducer percentage.
S668 Calculated Airflow—Shows the calculated airflow based on the low, high, number of EC fans
and the Inlet Ring K-Value settings.
Figure 130
Sensor calibration/setup screen, page 7 of 7
S670 SP Transducer is Connected to—Sets the analog input that will be used for the static
pressure transducer. This parameter is selectable from None, Ana In 1, Ana In 2, Ana In 3 and Ana In
4. The default is none.
S671 SP Transducer Setup in—Sets the unit of measure that will be used for the static pressure
transducer. This parameter is selectable in inWC or PA. The default is PA.
S672 SP Transducer Low—Calibrates the static pressure transducer. Sets the value displayed at
the starting point of the analog input signal. This parameter is selectable from 0-9.999 inWC or
0.0 - 2491.0 Pa. The default is 0.000 inWC or 0.0 Pa.
S673 SP Transducer High—Calibrates the static pressure transducer. Sets the maximum value
displayed, or end point of the analog input. This parameter is selectable from 0-9.999 inWC or
0.0 - 2491.0 Pa. The default is 2.005 inWC or 500.0 Pa.
S677 Results:—Read-only string that describes S678 through S681.
S678 SP Transducer Low—Shows the status of the low static pressure transducer in both inWC
and Pa after it's setup at S672.
S679 SP Transducer High—Shows the status of the high static pressure transducer in both inWC
and Pa after it's setup at S673.
S680 Actual SP Signal—Shows the actual static pressure transducer percentage.
S681 Current Static Pressure—Shows the current static pressure based on low and high settings.
®
®
145
Liebert
iCOM
for Liebert DSE