Service menus allow customized settings for site operations. The password for service menu
parameters is 5010.
The Liebert iCOM firmware is being updated constantly. As a result, the Service menu parameter
tables shown in this manual may be slightly different than what is shown on your cooling unit's
display. Please check

Figure 81 Service Menu Main Screen

8.1

Service-Setpoints Menu Screens

Setpoints allow the user to view, change and set all temperature- and humidity-related parameters.

Figure 82 Setpoints screen, page 1 of 9

S102 Temperature Control Sensor—Selects which sensor will be controlling the cooling capacity.
Cooling capacity is either the Chilled Water Valve, Compressor, FreeCooling Valve or Air
Economizer. Unloading type compressors can be set to any sensor type, however fixed style
®
®