5.3
Wiring for Unit-to-Unit Communications—U2U
Cooling units come from the factory-wired for stand-alone operation.
Liebert iCOM U2U Ethernet Network
The Liebert iCOM U2U network must be isolated from other network traffic. The network switch(es)
that connect Liebert iCOMs need to be dedicated to supporting only Liebert iCOM communication.
The U2U network cannot be connected to the building or IT network. If network communication is
ever lost (failed network switch, etc.), all Liebert iCOM-controlled cooling units will continue to
operate as independent units.
The Liebert iCOM can support up to 64 nodes on one network. An input/output board, large display,
and large wall-mount display are each considered one node. Of the 64 nodes that may be connected,
no more than 32 may be input/output boards (32 cooling units). The following table illustrates how a
network can be configured.
Table 23
Sample Liebert iCOM network configurations
Sample
Configuration
1
2
3
4
5
6
7
8
Network communication can be configured during system startup by a Liebert-trained technician. For
technical issues contact:
Emerson Technical Service
1050 Dearborn Drive
Columbus, Ohio 43235
Telephone: 1-800-LIEBSRV (1-800-543-2778)
E-Mail:
technicalservice@emersonnetworkpower.com
Input/Output
Large
Boards
Displays
2
0
2
0
3
0
2
1
8
4
32
32
32
27
32
0
85
Installing a Liebert iCOM Unit-to-Unit Network
Wall Mount
Private
Large
Switch
Displays
Required
0
No
1
Yes
0
Yes
0
Yes
1
Yes
0
Yes
5
Yes
32
Yes
®
Liebert
iCOM
®
for Liebert DSE