Service-Set Alarms Menu Screens

Set Alarms allows the user to view and modify critical alarm thresholds, time delays, enable/disable
alarms, modify event types and program custom alarm inputs.
Figure 109
Set alarms screen, page 1 of 12
S202 Return Sensor Alarms—Enables and disables the return temperature and humidity sensor
alarms. Default is Enabled.
S203 High Return Temperature—Sets the threshold temperature when a return high
temperature alarm will occur.
S204 Low Return Temperature—Sets the threshold temperature when a return low temperature
alarm will occur.
S205 High Return Humidity—Sets the threshold humidity when a return high humidity alarm
will occur.
S206 Low Return Humidity—Sets the threshold humidity when a return low humidity alarm will
occur.
S207 Sensor A Alarms—Enables or disables the alarms associated with Sensor A if the unit is
equipped with the optional temperature / humidity sensor.
S208 High Temperature Sensor A—Sets the threshold temperature when a Sensor A high
temperature alarm will occur.
S209 Low Temperature Sensor A—Sets the threshold temperature when a Sensor A low
temperature alarm will occur.
S210 High Humidity Sensor A—Sets the threshold humidity when a Sensor A humidity alarm will
occur.
S211 Low Humidity Sensor A—Sets the threshold humidity when a Sensor A low humidity alarm
will occur.
S21A Loss of Flow Compressor Timer—Allows setting a maximum pumpdown time during a loss
of flow condition to prevent causing a high pressure alarm due to pumpdown with no water/glycol flow
to the condenser; hidden unless pumpdown is enabled; applies only to water-cooled systems.
S21B Loss of Flow CFC Threshold—Sets the threshold for CFC loss of flow.
®
®