Figure 127 Sensor Calibration/Setup Screen - Emerson Liebert iCOM Manual

Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

Service Menu Parameters
S628 Supply/Return Sensor—Adjusts the supply temperature reading from the actual sensor to
compensate for any sensor error or to match other sensors in the room.
S629 Calibrated Supply Sensor—Shows the adjusted temperature value of the supply sensor. This
value is the actual sensor reading (+ or -) the offset "Supply Sensor".
S630 Offset Outdoor Temperature—Adjusts the outdoor temperature reading from the actual
sensor reading to compensate for any sensor error or to match other sensors.
S631 Calibrated Outdoor Temperature—Shows the adjusted temperature value of the outdoor
temperature. This value is the actual sensor reading (+ or -) the "Offset Outdoor Temperature".
S632 Offset Outdoor Humidity—Adjusts the outdoor humidity reading from the actual sensor
reading to compensate for any sensor error or to match other sensors.
S633 Calibrated Outdoor Humidity—Shows the adjusted humidity value of the outdoor humidity
sensor. This value is the actual sensor reading (+ or -) the "Offset Outdoor Humidity".
S63A Optional Sensor C2T—Shows the adjusted temperature value of the sensor C. This value is
the actual sensor reading (+ or -) the "Calibrated Optional Sensor C2T".
S63B Calibrated Optional Sensor C2T—Adjusts the optional sensor C2T reading from the actual
sensor reading to compensate for any sensor error or to match other sensors.
Figure 127
Sensor calibration/setup screen, page 4 of 7
®
®
143
Liebert
iCOM
for Liebert DSE