Parameterization

7 Detector empty pipe
(menu item "Detector e. pipe"), for devices with meter size DN10 and larger
The measuring tube for the flowmeter primary must be full. Select the menu "Detector e.
pipe". Next press ENTER. Use the STEP key to call up "Adjust detector e. pipe" and select
ENTER to start the adjustment. A number is displayed. Use the STEP or DATA key to
change to the value 2000 ±  2 5 Hz. To accept this value, press ENTER.
Now empty the pipeline. The adjustment value displayed must rise above the value set in the
"Threshold" menu. This ensures the empty pipe detector is adjusted.
Note
When configuration is complete, all data must be saved. To do so, call up the menu item
"Save data to ext. EEPROM" and select ENTER.
5
Parameterization
5.1

Data entry

Use the keys (3) to enter data when housing is open. If closed, use the magnet stick (6) and the
magnet sensors. The stick is held over the appropriate NS symbol.
Fig. 29
1 Plug-in EEPROM
2 Magnet sensor DATA/ENTER
3 Operator keys
26 - EN
Standard application
1
2
6
FXE4000 (COPA-XE/MAG-XE)
5
3
4
4 Magnet sensor STEP
5 Magnet sensor C/CE
6 Magnet
G00148
D184B133U02