N L1
1
2
S1 S2
<5°
Tf
Tf
LED
~
- +
1
2
S1 S2
<5°
Tf
Tf
LED
Nominal voltage
Power consumption - motoring
- holding
Dimensioning
Protection class
Degree of protection
Running time - motor
- spring return
Ambient temperature
- normal duty
- safety duty
- non-operating temperature
Connecting - motor
- auxiliary switch
Thermal trips
S3
S4
S5
S6
<80°
BAT
S3
S4
S5
S6
<80°
BAT
AC 230 V 50/60 Hz
3,5/5 W
1,1/2,1 W
6,5/10 VA (Imax 4 A @ 5 ms)
The safe position will be attained up to max. +75°C
cable 1 m, 2 x 0,75 mm² (BFL 24-T-ST) with 3-pin plug-in connectors
cable 1 m, 6 x 0,75 mm² (BFL 24-T-ST) with 6-pin plug-in connectors
4/6 VA (Imax 8,3 A @ 5 ms)
II
IP 54
<60 s
~ 20 s
- 30°C ... +55°C
- 40°C ... +55°C
duct outside temperature +72°C
duct inside temperature +72°C
5
AC 24 V 50/60 Hz
DC 24 V
2,5/4 W
0,8/1,4 W
III

Advertisement