Mandik FDMC Manual page 18

Fire damper
Hide thumbs Also See for FDMC:
Table of Contents

Advertisement

≥ 10
≥ 10
POSITION:
1
Fire damper FDMC
2
Mortar or gypsum
3
Mineral stone wool min. density 140 kg/m
D-20
(≥ 100)+50
Gap between damper and construction is filled by mortar or
gypsum and mineral wool
Wool is fixed to damper body and construction by fire protection
mastic.
Mineral wool thickness = construction thickness + 50 mm
Installation is valid for ceiling construction
3
18
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
≥ 100
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
≥ 100