Connecting and commissioning
5.5 Commissioning
Station/Power
Entering the maximum current for each outer conductor
Only a qualified electrician can make an entry in this field.
Enter the maximum available current for each phase in mA for the charging station. The
value must not exceed the rated current of the back-up fuse.
When operating two SICHARGE charging stations on one backup fuse:
The sum of maximum currents of the two SICHARGE charging stations must not exceed the
rated current of the backup fuse.
Setting values:
• Min. = 6000 mA
• Max. = 63000 mA or rated current of the back-up fuse if the back-up fuse is less than 63 A
Pressing the "Save" button saves the entry in the charging station.
Use "Reload" button to retrieve and display the value from the charging station.
Figure 5-14
Station Power
64
WARNING
SICHARGE Operating instructions, ERK
Operating Instructions, 06/2021, A5E48571690-AC