Connecting The Electronic Insert Fei53 (3-Wire) - Endress+Hauser Liquicap M FTI51 Operating Instructions Manual

Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Liquicap M FMI51, FMI52
Endress+Hauser
4.7
Connecting the electronic insert FEI53 (3–WIRE)
The 3-wire DC connection is used in conjunction with the Nivotester switching device FTC325 3–
WIRE from Endress+Hauser; the switching device's communication signal operates at 3 to 12 V.
The changeover of fail-safe mode (MIN) / (MAX) and the level limit calibration take place on the
Nivotester.
Power supply
DC voltage: 14.5 V
Current consumption: < 15 mA
Power consumption: max. 230 mW
Reverse polarity protection: yes
Separation voltage: 0.5 kV
Signal on alarm
< 2.7 V
Connectable load
• Floating relay contacts in the connected switching unit Nivotester FTC325 3–WIRE
• For the contact load capacity, refer to the technical data of the switching device.
Connect the FEI53 (3-WIRE) as follows:
1.
Make the connection as shown in the graphic.
2.
Turn the cable gland until tight.
!
Note!
Do not switch on the supply voltage until you have
familiarized yourself with the device functions as
described in chapter 5, "Operation". This will ensure
that you do not accidentally trigger any processes by
switching on the supply voltage.
3.
Switch on the supply voltage.
FEI53
1 2
3
(+)
12 11 13
Nivotester FTC325 3-WIRE
+
S
L00–FTI5xxxx–04–05–xx–xx–003
Wiring
43