Configuration instructions

3.7.1
Installation instructions
Liquicap M FTI51 (rod probe) can be installed from above, from below and from the side.
Liquicap M FTI52 (rope probe) can be installed vertically from above.
Note!
• The probe may not come into contact with the container wall! Do not install probes in the area
of the filling curtain!
• When using in agitating tanks, make sure you install at a safe distance from the agitator. If there
are strong lateral loads, use rod probes with ground tube.
For electrically conductive tanks, e.g. steel tanks
MAX
MAX
MIN
MIN
For non-conductive tanks, e.g. plastic tanks
MAX
MAX
Probes with ground tube and grounding
Liquicap M FMI51, FMI52
MAX
MAX
MIN
MIN
MAX
MAX
MIN
MIN
L00–FTI5xxxx–11–06–xx–xx–001