Endress+Hauser
• If the wires are not reused, the crimp connections of the newly attached eyelets must be insulated,
for example using a heat-shrinking sleeve (danger of short circuit).
• All soldered joints must be insulated.
3.12

Probe with active build-up compensation

1. Pressing screw
2. Insert seal
3. Cabel gland
4. Heatshrinking sleeve
5. Seal
6. Adapter disk
7. Seal
8. Plug M3
9. Split washer
10. Strand yellow/green (YE/GN) with ring terminal
11. Strand yellow (YE) soldered with the guard strand,
insulated with a heatshrinking sleeve
12. Snap ring
13. Nut M4
14. Split washer
15. Strand red (RD) with ring terminal
insulated with a heatshringking sleeve
16. Blade plug
17. Guard strand (rd)
18. Tube
19. Process connection
3.12.1
Shortening the connecting cable
Note!
The maximum connection length between the probe and separate housing is 6 m and is indicated
by dimension L4. The connection length must be quoted when ordering a Liquicap M with a
separate housing.
If the connecting cable is to be shortened or guided through a wall, it must be disconnected from
the process connection. To do so, proceed as follows:
• Unscrew the pressure screw (1) using a 22mm open-end wrench. If necessary, hold the process
connection. In doing so, ensure that neither the connecting cable nor the probe is turned in the
process.
• Pull the insert seal (2) out of the cable gland (3).
• Using a 22mm open-end wrench, disconnect the cable gland (3) from the adapter disc. If
necessary, hold it against the adapter disc (6) using a 34mm open-end wrench.
• Disconnect the adapter disc (6) from the sleeve (17).
• Remove the snap ring using a snap ring pliers.
RD
YE
25. Solder the
red (RD)
with the central core of the
coaxial cable (probe)
GN/YE
24. Solder the
yellow (YE)
with the
guard
from the tube.
23. Strand yellow/green (YE/GN)
with a ring terminal
22. Coaxial cable with
a
nd
screening
21. Strand black (BK)
(not required)
20. External screening
(not required)
Installation
strand
strand
strand (RD)
central core
BA299Fen014