Before you transfer the UPS from maintenance bypass mode to normal mode,
ensure that the bypass input and output are normal.
Procedure
Step 1 Turn off the maintenance bypass switch.
Step 2 Start the inverter.
----End

4.9 Performing EPO

● After the EPO button is turned on, the UPS supplies no power and the loads
● In maintenance bypass mode, the UPS continues to supply power even after
Press the external EPO switch that connects to the dry contact card or remove the
4-pin terminal on the EPO port of the dry contact card.
Figure 4-15 EPO ports
After you press the EPO button, the EPO and No power supplied alarms are
displayed on the LCD.

4.10 Clearing the EPO State

Procedure
Step 1 Clear the EPO state. Ensure that the EPO button connected to the dry contact is
not in the EPO state.
Issue 07 (2022-06-20)
NO TICE
NO TE
The Maint. breaker closed alarm disappears from the MDU.
NO TICE
shut down.
the EPO button is turned on.