Troubleshooting - Huawei UPS5000-E-30 kVA-FM User Manual

Table of Contents

Advertisement

UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
● If the UPS is faulty, alarm information is displayed on the LCD. The UPS can be
● Do not clear alarms by reseating modules.
● Remove a faulty module after confirming that it needs to be replaced. After
● After a UPS finishes troubleshooting and is started, if the LCD continues
● When batteries reach EOD, the battery switch in the BCB box trips if the BCB
● To restore battery discharge after batteries reach EOD, use one of the following
For details about how to rectify common faults, see
unmentioned faults occur, see the alarm list or contact technical support.
Issue 03 (2022-01-30)
CA UTION
powered on only after critical alarms are handled. Failing to do so may escalate
faults or damage the equipment.
removing the module, do not insert it into the UPS again.
NO TICE
displaying alarm information, choose System Info > Alarms > Clear Faults to
clear the alarm and then start the inverter.
box is configured. To restore battery discharge, turn on the battery switch in the
BCB box.
methods: 1. Switch to another battery string. Ensure that each battery has a
voltage greater than the EOD voltage and 11.3 V/cell. 2. Restore the mains
power supply to start the inverter. Turn on the battery switch and charge
batteries until each battery has a voltage greater than the EOD voltage and
11.3 V/cell.
Copyright © Huawei Technologies Co., Ltd.
6

Troubleshooting

Table
6 Troubleshooting
6-1. If any
117

Advertisement

Table of Contents
loading

Table of Contents