UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
Port
Battery
input
Output
PE
Table 3-4 Recommended upstream input and downstream output circuit breakers
UPS Capacity
30 kVA
60 kVA
90 kVA
120 kVA
a: recommended when the short-circuit current where the switch is located is
less than 36 kA
Issue 03 (2022-01-30)
Connection
Bolt
Method
Specifications
Crimped OT
M12
terminals
Crimped OT
M10
terminals
Crimped OT
M10
terminals
Component
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Copyright © Huawei Technologies Co., Ltd.
Bolt Hole
Bolt Length
Diameter
13 mm
35 mm
11 mm
30 mm
11 mm
30 mm
Specifications
63 A/3P
63 A/3P
63 A/3P
125 A/3P
125 A/3P
125 A/3P
200 A/3P
200 A/3P
200 A/3P
250 A/3P
250 A/3P
250 A/3P
3 Installation
Torque
46 N·m
26 N·m
26 N·m
a
51